                  Device number in electrical system descriptions IEEE Std C37.2-1996

 

 Standard device function numbers

                  Each number, with its corresponding function name and a general description of  

              the function, is listed below.

 

                NOTE — When alternate names and descriptions are included under the function, only the name and description that applies to each specific case should be used. In general, only one name for each device, such as relay, contactor, circuit breaker, switch, or monitor, is included in each function designation. However, when the function is not inherently restricted to any specific type of device, and where the type of device itself is thus merely incidental, any one of the above listed alternative names, as applicable, may be substituted. For example, if for device function 6 a contactor is used for the purpose in place of a circuit breaker, the function name should be specified as “starting contactor.” device function numbers, the originator should provide a brief definition for all device function numbers used in that application, including all combinations of prefixes, function numbers, and suffixes These definitions should be included in the drawing where the device function number is used, or in a separate drawing or list to which the other drawings refer. All instruction books and other documents shall also include the device function number definitions. Numbers from 95 through 99 should be assigned only for those functions in specific cases where none of the assigned standard device function numbers are applicable. Numbers that are “reserved for future application” should not be used.

 

 Device number 1—master element  A device, such as a control switch, etc., that

                                     serves, either directly or through such permissive devices as

                                     protective and time-delay relays, to place equipment in or out of

                                     operation.

Device number 2—time-delay starting or closing relay  A device that functions

                                    to give a desired amount of time delay before or after any point of

                                    operation in a switching sequence or protective relay system,

                                    except as specifically provided by device functions 48, 62,

                                    79, and 82.

Device number 3—checking or interlocking relay  A device that operates in

                                     response to the position of one or more other devices or

                                     predetermined conditions in a piece of  equipment or circuit, to

                                    allow an operating sequence to proceed, or to stop, or to

                                     provide a check of the position of these devices or conditions for

                                    any purpose.

 

Device number 4—master contactor  A device, generally controlled by device

                                    function l or the equivalent and the required permissive and

                                    protective devices, that serves to make  and break the necessary

                                    control circuits to place equipment into operation under the

                                    desired conditions and to take it out of operation under abnormal

                                    conditions.

Device number 5—stopping device  A control device used primarily to shut down

                                    equipment and hold it out of operation. (This device may be

                                    manually or electrically actuated, but it excludes the function of

                                   electrical lockout [see device function 86] on abnormal conditions.)

Device number 6—starting circuit breaker A device whose principal function is to

                                    connect a machine to its source of starting voltage.

Device number 7—rate-of-change relay  A device that operates when the rate-of-

                                    change of the measured quantity exceeds a threshold value, except

                                   as defined by device 63 .

Device number 8—control power disconnecting device A device, such as a

                                    knife switch, circuit breaker, or pull-out fuse block, used for the

                                    purpose of connecting and disconnecting the source of control

                                   power to and from the control bus or equipment.

                                   NOTE — Control power is considered to include auxiliary power

                                                   that supplies such apparatus   as small motors and heaters.

Device number 9—reversing device  A device that is used for the purpose of

                                    reversing a machine field or for performing any other reversing

                                   function.

Device number 10—unit sequence switch  A device that is used to change the

                                     sequence in which units may be placed in and out of service in

                                    multiple-unit equipment.

Device number 11—multifunction device A device that performs three or more

                                     Comparatively important functions that could only be designated

                                     by combining several device function numbers. All of the

                                    functions performed by device 11 shall be defined in  the drawing

                                    legend, device function definition list or relay setting record.

                                      NOTE — If only two relatively important functions are p

                                                        performed by the device, it is preferred that both

                                                        function numbers be used.

Device number 12—overspeed device  A device, usually direct connected, that

                                      operates on machine  overspeed.

Device number 13—synchronous-speed device  A device such as a centrifugal-

                                       speed switch, a slip-frequency relay, a voltage relay, an

                                       undercurrent relay, or any other type of device that operates at   

                                       approximately the synchronous speed of a machine.

 Device number 14—under speed device  A device that functions when the speed of

                                      a machine falls below a predetermined value.

Device number 15—speed or frequency matching device A device that

                                      functions to match and hold the speed or frequency of a machine

                                      or a system equal to, or approximately equal to, that of another

                                      machine, source, or system.

Device number 16—not used  Reserved for future application.

Device number 17—shunting or discharge switch  A device that serves to open

                                     or close a shunting circuit around any piece of apparatus (except a

                                     resistor), such as a machine field, a machine armature, a capacitor,

                                     or a reactor.

                                          NOTE — This excludes devices that perform such shunting

                                                           operations as may be necessary in the process of

                                                           starting a machine by devices 6 or 42 (or their

                                                           equivalent) and also excludes device function 73 that

                                                           serves for the switching of resistors.

Device number 18—accelerating or decelerating device  A device that is used

                                      to close or cause the closing of circuits that are used to increase or

                                      decrease the speed of a machine.

Device number 19—starting-to-running transition contactor  A device that

                                      operates to initiate or cause the automatic transfer of a machine

                                      from the starting to the running power connection.

Device number 20—electrically operated valve   An electrically operated,

                                      controlled, or monitored device used in a fluid, air, gas, or

                                     vacuum line.

Device number 21—distance relay   A device that functions when the circuit

                                      admittance, impedance,or reactance increases or decreases

                                      beyond a predetermined value.

Device number 22—equalizer circuit breaker  A device that serves to control or

                                     make and break the equalizer or the current-balancing connections

                                     for a machine field, or for regulating equipment, in a multiple-unit

                                     installation.

 Device number 23—temperature control device  A device that functions to

                                     control the temperature  of a machine or other apparatus, or of any

                                     medium, when its  temperature falls below or rises above a

                                     predetermined value.

                                      NOTE — An example is a thermostat that switches on a space

                                                       heater in a switchgear  assembly when the temperature

                                                       falls to a desired value. This should be distinguished

                                                      from a device that is used to provide automatic

                                                      temperature regulation between close limits and would    

                                                      be designated as device function 90T.

 

Device number 24—volts per hertz relay A device that operates when the ratio of

                                      voltage to  frequency is above a preset value or is below a

                                      different preset value. The relay may have any combination of

                                      instantaneous or time delayed characteristics.

Device number 25—synchronizing or synchronism-check relay

                                  A synchronizing device produces an output that causes closure at

                                      zero-phase angle difference between two circuits. It may or may

                                     not include voltage and speed control. A synchronism- check relay

                                     permits the paralleling of two circuits that are within prescribed

                                     limits of voltage magnitude, phase angle, and frequency.

Device number 26—apparatus thermal device   A device that functions when the

                                      temperature of the protected apparatus (other than the load-

                                      carrying windings of machines and transformers as covered by

                                     device function number 49) or of a liquid or other  medium

                                     exceeds a predetermined value; or when the temperature of the

                                     protected apparatus or of any medium decreases below a

                                     predetermined value.

Device number 27—undervoltage relay  A device that operates when its input

                                     voltage is less than a predetermined value.

Device number 28—flame detector  A device that monitors the presence of the pilot

                                     or main flame in  such apparatus as a gas turbine or a steam boiler.

Device number 29—isolating contactor or switch  A device that is used

                                      expressly for disconnecting one circuit from another for the

                                      purposes of emergency operation, maintenance, or  test.

Device number 30—annunciator relay  A nonautomatically reset device that gives

                                     a number of separate visual indications upon the functioning of

                                     protective devices and that may  also be arranged to perform a

                                     lockout function.

Device number 31—separate excitation device  A device that connects a circuit,

                                     such as the shunt field of a synchronous converter, to a source of

                                     separate excitation during the starting sequence.

Device number 32—directional power relay  A device that operates on a

                                      predetermined value of power flow in a given direction such as

                                      reverse power flow resulting from the motoring of a generator

                                     upon loss of its prime mover.

Device number 33—position switch  A device that makes or breaks contact when

                                    the main device or piece of apparatus that has no device function

                                    number reaches a given position.

 Device number 34—master sequence device  A device such as a motor-operated

                                     multi-contact switch, or the equivalent, or a programmable device,

                                     that establishes or determines the operating sequence of the major

                                    devices in equipment during starting and stopping or during

                                    sequential switching operations.

Device number 35—brush-operating or slip-ring short-circuiting device

                                  A device for raising, lowering, or shifting the brushes of a

                                     machine; short-circuiting its slip rings; or engaging or disengaging

                                     the contacts of a mechanical rectifier.

Device number 36—polarity or polarizing voltage device  A device that

                                     operates, or permits the operation of, another device on a

                                     predetermined polarity only or that verifies the  presence of a

                                     polarizing voltage in equipment.

Device number 37—undercurrent or underpower relay   A device that functions

                                      when the current or power flow decreases below a predetermined

  value.

Device number 38—bearing protective device     A device that functions on

                                      excessive bearing temperature or on other abnormal mechanical

                                      conditions associated with the bearing, such as undue wear,

                                      which may eventually result in excessive bearing

                                      temperature or failure.

Device number 39—mechanical condition monitor  A device that functions upon

                                      the occurrence of an abnormal mechanical condition (except that

                                      associated with bearings as covered  under device function 38),

                                      such as excessive vibration, eccentricity, expansion,  shock,

                                      tilting, or seal failure.

Device number 40—field relay  A device that functions on a given or abnormally

                                     high or low value or failure of machine field current, or on an

                                     excessive value of the reactive component  of armature current in

                                    an ac machine indicating abnormally high or low field excitation.

Device number 41—field circuit breaker   A device that functions to apply or

                                      remove the field excitation of a machine.

Device number 42—running circuit breaker    A device whose function is to

                                     connect a machine to its source of running or operating voltage.

                                     This function may also be used for a device,    such as a contactor,

                                    that is used in series with a circuit breaker or other fault- protecting

                                    means, primarily for frequent opening and closing of the circuit.

Device number 43—manual transfer or selector device  A manually operated

                                     device that transfers control or potential circuits in order to modify

                                      the plan of operation of the associated equipment or of some of

                                    the associated devices.

 Device number 44—unit sequence starting relay   A device that functions to start

                                      the next available unit in multiple-unit equipment upon the failure

                                     or non-availability of the normally Preceding unit.

Device number 45—atmospheric condition monitor   A device that functions

                                      upon the occurrence of an abnormal atmospheric condition, such

                                     as damaging fumes, explosive  mixtures, smoke, or fire.

Device number 46—reverse-phase or phase-balance current relay   A device

                                      in a polyphase circuit that operates when the polyphase currents

                                     are of reverse-phase sequence or when the polyphase currents are

                                     unbalanced or when the negative phase-sequence current exceeds

                                     a preset value.

Device number 47—phase-sequence or phase-balance voltage relay

                                 A device in a polyphase circuit that functions upon a redetermined

                                     value of polyphase voltage in the desired phase sequence, when

                                     the polyphase voltages are unbalanced, or when the negative

                                    phase-sequence voltage exceeds a preset value.

Device number 48—incomplete sequence relay   A device that generally returns

                                     the equipment to  the normal or off position and locks it out if the

                                     normal starting, operating, or stopping sequence is not properly

                                     completed within a predetermined time.

 Device number 49—machine or transformer thermal relay  A device that

                                       functions when the temperature of a machine armature winding

                                       or other load-carrying winding or element of a machine or power

                                     transformer exceeds a predetermined value.

Device number 50—instantaneous overcurrent relay 

                                 A device that operates with no intentional   time delay when the

                                     current exceeds a preset value.

Device number 51—ac time overcurrent relay    A device that functions when the

                                      ac input current exceeds a predetermined value, and in which the

                                      input current and operating time are inversely related through a

                                      substantial portion of the performance range.

Device number 52—ac circuit breaker    A device that is used to close and

                                     interrupt an ac power circuit under normal conditions or to

                                     interrupt this circuit under fault or emergency  conditions.

Device number 53—exciter or dc generator relay   A device that forces the dc

                                       machine field  excitation to build up during starting or that

                                       functions when the machine voltage has built up to a given value.

Device number 54—turning gear engaging device     A device either electrically

                                      operated, controlled, or monitored that functions to cause the

                                      turning gear to engage (or disengage) the machine shaft.

Device number 55—power factor relay   A device that operates when the power

                                      factor in an ac circuit rises above or falls below a predetermined

                                      value.

Device number 56—field application relay    A device that automatically controls

                                      the application of the field excitation to an ac motor at some

                                       predetermined point in the slip cycle.

Device number 57—short-circuiting or grounding device   A device that

                                      functions to short-circuit or ground a circuit in response to

                                      automatic or manual means.

Device number 58—rectification failure relay    A device that functions if a power

                                      rectifier fails to conduct or block properly.

Device number 59—overvoltage relay        A device that operates when its input

                                      voltage exceeds a  predetermined value.

Device number 60—voltage or current balance relay  A device that operates on

                                       a given difference  in voltage, or current input or output, of two

                                       circuits.

Device number 61—density switch or sensor   A device that operates at a given

                                      density value or at  a given rate of change of density.

Device number 62—time-delay stopping or opening relay  A device that

                                      imposes a time delay in conjunction with the device that initiates

                                      the shutdown, stopping, or opening operation in an automatic

                                      sequence or protective relay system.

Device number 63—pressure switch   A device  that operates at a given pressure

                                      value or at a given  rate of change of pressure.

Device number 64—ground detector relay  A device that operates upon failure of

                                      machine or other apparatus insulation to ground.

                                           NOTE — This function is not applied to a device connected in

                                                             the secondary circuit of current transformers in a

                                                             normally grounded power system where other

                                                             vercurrent device numbers with the suffix G or N

                                                             should be used; for example,51N for an ac time

                                                             overcurrent relay connected in the secondary

                                                             neutral of the current transformers.

Device number 65—governor   A device consisting of an assembly of fluid,

                                       electrical, or mechanical control equipment used for regulating

                                       the flow of water, steam, or other media to the prime mover for

                                       such purposes as starting, holding speed or load, or stopping.

Device number 66—notching or jogging device  A device that functions to allow

                                      only a specified  number of operations of a given device or piece

                                      of equipment, or a specified number of successive operations

                                      within a given time of each other. It is also a device that functions

                                      to energize a circuit periodically or for fractions of specified

                                      time intervals, or that is used to permit intermittent acceleration

                                     or jogging of a  machine at low speeds for mechanical positioning.

Device number 67—ac directional overcurrent relay   A device that functions at

                                      a desired value of ac overcurrent flowing in a predetermined

                                      direction.

Device number 68—blocking or “out-of-step” relay   A device that initiates a

                                      pilot signal for blocking of tripping on external faults in a

                                     transmission line or in other apparatus under predetermined

                                     conditions, or cooperates with other devices to block tripping or

                                     reclosing on an outof- step condition or on power swings.

Device number 69—permissive control device  A device with two-positions that

                                      in one position permits the closing of a circuit breaker, or the

                                      placing of a piece of equipment into operation, and in the other

                                      position, prevents the circuit breaker or the equipment from being

                                     operated.

Device number 70—rheostat  A device used to vary the resistance in an electric

                                     circuit when the device is electrically operated or has other

                                     electrical accessories, such as auxiliary, position, or limit

                                     switches.

Device number 71—level switch   A device that operates at a given level value, or

                                     on a given rate of  change of level.

Device number 72—dc circuit breaker   A device that is used to close and interrupt

                                      a dc power circuit under normal conditions or to interrupt this

                                      circuit under fault or emergency  conditions.

Device number 73—load-resistor contactor  A device that is used to shunt or

                                      insert a step of load limiting, shifting, or indicating resistance in a

                                      power circuit; to switch a space heater in circuit; or to switch a

                                      light or regenerative load resistor of a power rectifier or other

                                      machine in and out of circuit.

Device number 74—alarm relay   A device other than an annunciator, as covered

                                      under device function 30, that is used to operate, or that operates

                                      in  connection with, a visual or audible alarm.

Device number 75—position changing mechanism   A device that is used for

                                      moving a main device from one position to another in equipment;

                                      for example, shifting a removable circuit breaker unit to and from

                                      the connected, disconnected, and test  positions.

Device number 76—dc overcurrent relay   A device that functions when the

                                      current in a dc circuit exceeds a given value.

Device number 77—telemetering device A transmitting device used to generate

                                      and transmit to a remote location an electrical signal representing

                                      a measured quantity; or a receiver used to receive the electrical

                                      signal from a remote transmitter and convert the signal

                                      to represent the original measured quantity.

Device number 78—phase-angle measuring relay   A device that functions at a

                                      predetermined phase angle between two voltages, between two

                                      currents, or between voltage and  current.

Device number 79—reclosing relay   A device that controls the automatic reclosing

                                      and locking out  of an ac circuit interrupter.

Device number 80—flow switch   A device that operates at a given flow value, or at

                                      a given rate of  change of flow.

Device number 81—frequency relay  A device that responds to the frequency of an

                                     electrical quantity, operating when the frequency or rate of change

                                     of frequency exceeds or is  less than a predetermined value.

Device number 82—dc load-measuring reclosing relay  A device that controls

                                     the automatic closing and reclosing of a dc circuit interrupter,

                                     generally in response to load circuit conditions.

Device number 83—automatic selective control or transfer relay  A device

                                     that operates to select automatically between certain sources or

                                     conditions in equipment or that performs a transfer operation

                                     automatically.

Device number 84—operating mechanism   A device consisting of the complete 

                                      electrical  mechanism or servomechanism, including the

                                      operating motor, solenoids, position switches, etc., for a tap

                                      changer, induction regulator, or any similar piece of  apparatus

                                     that otherwise has no device function number.

Device number 85—carrier or pilot-wire relay   A device that is operated or

                                      restrained by a signal transmitted or received via any

                                      communications media used for relaying.

Device number 86—lockout relay  A device that trips and maintains the associated

                                     equipment or devices inoperative until it is reset by an operator,

                                     either locally or remotely.

Device number 87—differential protective relay    A device that operates on a

                                      percentage, phase angle, or other quantitative difference of two or

                                     more currents or other electrical quantities.

Device number 88—auxiliary motor or motor generator  A device used for

                                     operating auxiliary equipment, such as pumps, blowers, exciters,

                                     rotating magnetic amplifiers, etc.

Device number 89—line switch   A device used as a disconnecting, load-interrupter,

                                     or isolating switch in an ac or dc power circuit. (This device

                                      function number is normally not  necessary unless the switch is

                                      electrically operated or has electrical accessories,  such as an

                                      auxiliary switch, a magnetic lock, etc.)

Device number 90—regulating device A device that functions to regulate a      

                                     quantity or quantities, such as voltage, current, power, speed,

                                      frequency, temperature, and load, at a  certain value or between

                                      certain (generally close) limits for machines, tie lines, or  other

                                    apparatus.

               

Device number 91—voltage directional relay   A device that operates when the

                                      voltage across an  open circuit breaker or contactor exceeds a

                                      given value in a given direction.

Device number 92—voltage and power directional relay   A device that permits

                                      or causes the  connection of two circuits when the voltage

                                     difference between them exceeds a given value in a predetermined

                                     direction and causes these two circuits to be disconnected from

                                     each other when the power flowing between them exceeds a

                                     given value in the opposite direction.

Device number 93—field-changing contactor    A device that functions to

                                     increase or decrease, in  one step, the value of field excitation on a

                                     machine.

Device number 94—tripping or trip-free relay  A device that functions to trip a

                                      circuit breaker, contactor, or equipment; to permit immediate

                                      tripping by other devices; or to prevent immediate reclosing of a

                                     circuit interrupter if it should open automatically, even though its

                                     closing circuit is maintained closed.

Device numbers 95–99—used only for specific applications   These device

                                                 numbers are used in  individual specific installations if 

                                                none of the functions assigned to the   numbers

                                                from 1 through 94 are suitable.

 Addition of prefixes and suffixes

      Letters and numbers may be used as prefixes or suffixes to device function numbers to provide a more specific definition of the function, as discussed below. They permit a manifold multiplication of available function designations for the large number and variety of devices used in the many types of equipment covered by this standard.

They may also serve to denote individual or specific parts or auxiliary contacts of these devices or certain distinguishing features, characteristics, or conditions that describe the use of the device or its contacts in the equipment. Prefixes and suffixes should, however, be used only when they accomplish a useful purpose. For example, when all of

the devices in a piece of equipment are associated with only one kind of apparatus, such as a feeder, motor, or  generator, it is common practice, in order to retain maximum simplicity in device function identification, not to add the respective suffix letters F, M, or G to any of the device function numbers.  In order to prevent any possible conflict or confusion, each letter suffix should preferably have only one meaning in

individual pieces of equipment.    However, each suffix should not consist of more than three (and preferably not more than two) letters, in order to keep the complete function designation as short and simple as possible. The meaning of each suffix should be designated on the drawings or in the publications with which they are used, similar to TC-trip coil, V-voltage, X-auxiliary relay.

            In cases where the same suffix (consisting of one letter or a combination of letters) has different meanings in the same equipment depending upon the device function number with which it is used, then the complete device function number with its suffix letter or letters and its corresponding function definition should be listed in the legend in each case, i.e., 63V-vacuum relay, 70R-raising relay for device 70, 90V-voltage regulator.

 Suggested prefixes

                    A similar series of numbers, prefixed by the letters RE (for remote) may be used for the interposing relays performing functions that are controlled directly from the supervisory system. Typical examples of such functions are RE1, RE5,

and RE94. In multiple-unit installations, it may be desirable to use a prefix number to distinguish between device functions associated with individual units. For example, in pipeline pump stations, the numbers 1–99 are applied to device functions that are associated with the overall station operation. A similar series of numbers, starting with 101 instead of 1, are used for those device functions that are associated with unit 1; a similar series starting with 201 for device functions that are associated with unit 2; and so on, for each unit in these installations.

 Suggested suffix letters

 Auxiliary devices

          These letters denote separate auxiliary devices, such as the following:

C Closing relay/contactor

CL Auxiliary relay, closed (energized when main device is in closed position)

CS Control switch

D “Down” position switch relay

L Lowering relay

O Opening relay/contactor

OP Auxiliary relay, open (energized when main device is in open position)

PB Push button

R Raising relay

U “UP” position switch relay

X Auxiliary relay

Y Auxiliary relay

Z Auxiliary relay

NOTE — In the control of a circuit breaker with a so-called X-Y relay control scheme, the X relay is the device whose main contacts are used to energize the closing coil or the device that in some other manner, such as by the release of stored energy, causes the breaker to close. The contacts of the Y relay provide the antipump feature of the circuit breaker.

Actuating quantities

These letters indicate the condition or electrical quantity to which the device responds, or the medium in which it is

located, such as the following:

A Air/amperes/alternating

C Current

D Direct/discharge

E Electrolyte

F Frequency/flow/fault

GP Gas pressure

H Explosive/harmonics

I0 Zero sequence current

I-, I2 Negative sequence current

I+, I1 Positive sequence current

J Differential

L Level/liquid

P Power/pressure

PF Power factor

Q Oil

S Speed/suction/smoke

T Temperature

V Voltage/volts/vacuum

VAR Reactive power

VB Vibration

W Water/watts

 Main device

The following letters denote the main device to which the numbered device is applied or is related:

A Alarm/auxiliary power

AC Alternating current

AN Anode

B Battery/blower/bus

BK Brake

BL Block (valve)

BP Bypass

BT Bus tie

C Capacitor/condenser/compensator/carrier current/case/compressor

CA Cathode

CH Check (valve)

D Discharge (valve)

DC Direct current

E Exciter

F Feeder/field/filament/filter/fan

14 Copyright ã 1997 IEEE All Rights Reserved

H Heater/housing

L Line/logic

M Motor/metering

MOC Mechanism operated contact4

N Network/neutral5

P Pump/phase comparison

R Reactor/rectifier/room

S Synchronizing/secondary/strainer/sump/suction (valve)

T Transformer/thyratron

TH Transformer (high-voltage side)

TL Transformer (low-voltage side)

TM Telemeter

TOC Truck-operated contacts6

TT Transformer (tertiary-voltage side)

U Unit

 Main device parts

These letters denote parts of the main device, except auxiliary contacts, position switches, limit switches, and torque

BK Brake

C Coil/condenser/capacitor

CC Closing coil/closing contactor

HC Holding coil

M Operating motor

MF Fly-ball motor

ML Load-limit motor

MS Speed adjusting or synchronizing motor

OC Opening contactor

S Solenoid

SI Seal-in

T Target

TC Trip coil

V Valve

Other suffix letters

A Accelerating/automatic

B Blocking/backup

BF Breaker failure

C Close/cold

D Decelerating/detonate/down/disengaged

E Emergency/engaged

F Failure/forward

GP General purpose

H Hot/high

3Suffix N is preferred when the device is connected in the residual of a polyphase circuit, is connected across a broken delta, or is internally derived from the polyphase current or voltage quantities. The suffix G is preferred where the measured quantity is in the path to ground or, in the case of ground fault detectors, is the current flowing to ground. See A.2 in Annex A for examples. 4MOC denotes a circuit breaker mechanism-operated auxiliary switch that is mounted on the stationary housing of a removable circuit breaker.

6TOC denotes a circuit breaker truck-operated auxiliary switch that is mounted on the stationary housing of a removable circuit breaker.

HIZ High impedance fault

HR Hand reset

HS High speed

L Left/local/low/lower/leading

M Manual

O Open/over

OFF Off

ON On

P Polarizing

R Right/raise/reclosing/receiving/remote/reverse

S Sending/swing

SHS Semi-high speed

T Test/trip/trailing

TDC Time-delay closing contact

TDDO Time delayed relay coil drop-out

TDO Time-delay opening contact

TDPU Time delayed relay coil pickup

THD Total harmonic distortion

U Up/under

Suffix numbers

If two or more devices with the same function number and suffix letter (if used) are present in the same piece of equipment, they may be distinguished by numbered suffixes, as, for example, 4X-1, 4X-2, and 4X-3, when necessary.

 Devices performing more than one function

If one device performs two important functions in a piece of equipment so that it is desirable to identify both of these functions, a double function number and name, such as 50/51 instantaneous and time overcurrent relay may be used.

 Device contacts

 Auxiliary, position, and limit switch contacts

The letters a and b shall be used for all auxiliary, position, and limit switch contacts for such devices and equipment as circuit breakers, contactors, valves and rheostats, and contacts of relays as follows:

a Contact that is open when the main device is in the standard reference position, commonly referred to as the nonoperated or de-energized position, and that closes when the device assumes the opposite position b Contact that is closed when the main device is in the standard reference position, commonly referred to as the non

Operated or de-energized position, and that opens when the device assumes the opposite position

The simple designation a or b is used in all cases where there is no need to adjust the contacts to change position at any particular point in the travel of the main device or where the part of the travel where the contacts change position is of

no significance in the control or operating scheme. Hence, the a and b designations usually are sufficient for circuit breaker auxiliary switches.