Device number in electrical system
Device number in electrical system descriptions IEEE Std C37.2-1996
Standard device function numbers
Each number, with its
corresponding function name and a general description of
the function, is listed below.
NOTE — When alternate names and descriptions are included under the
function, only the name and description that applies to each specific case
should be used. In general, only one name for each device, such as relay,
contactor, circuit breaker, switch, or
monitor, is included in each function designation. However, when the function
is not inherently restricted to any specific type of device, and where the type
of device itself is thus merely incidental, any one of the above listed alternative
names, as applicable, may be substituted. For example, if for device function 6
a contactor is used for the purpose in place of a circuit breaker, the function
name should be specified as “starting contactor.” device function numbers, the originator
should provide a brief definition for all device function numbers used in that
application, including all combinations of prefixes, function numbers, and
suffixes These definitions should be included in the drawing where the device
function number is used, or in a separate drawing or list to which the other
drawings refer. All instruction books and other documents shall also include
the device function number definitions. Numbers from 95 through 99 should be
assigned only for those functions in specific cases where none of the assigned
standard device function numbers are applicable. Numbers that are “reserved for
future application” should not be used.
Device number 1—master element A device, such as a control switch, etc., that
serves, either directly or
through such permissive devices as
protective
and time-delay relays, to place equipment in or out of
operation.
Device
number 2—time-delay starting or closing relay
A device that
functions
to give a
desired amount of time delay before or after any point of
operation
in a switching sequence or protective relay system,
except as
specifically provided by device functions 48, 62,
79, and 82.
Device
number 3—checking or interlocking relay A device that operates in
response to the position of one or more
other devices or
predetermined conditions in a piece of
equipment or circuit, to
allow an
operating sequence to proceed, or to stop, or to
provide a
check of the position of these devices or conditions for
any
purpose.
Device
number 4—master contactor A device, generally controlled by device
function
l or the equivalent and the required permissive and
protective
devices, that serves to make and break
the necessary
control
circuits to place equipment into operation under the
desired
conditions and to take it out of operation under abnormal
conditions.
Device
number 5—stopping device A control device used primarily to shut down
equipment
and hold it out of operation. (This device may be
manually or
electrically actuated, but it excludes the function of
electrical
lockout [see device function 86] on abnormal conditions.)
Device
number 6—starting circuit breaker A device whose principal function is to
connect a
machine to its source of starting voltage.
Device
number 7—rate-of-change relay A device that operates when the rate-of-
change of
the measured quantity exceeds a threshold value, except
as defined
by device 63 .
Device
number 8—control power disconnecting device A device, such as a
knife
switch, circuit breaker, or pull-out fuse block, used for the
purpose of
connecting and disconnecting the source of control
power to and from the control bus or
equipment.
NOTE —
Control power is considered to include auxiliary power
that supplies such apparatus as
small motors and heaters.
Device
number 9—reversing device A device that is used for the purpose of
reversing a
machine field or for performing any other reversing
function.
Device
number 10—unit sequence switch A device that is used to change the
sequence
in which units may be placed in and out of service in
multiple-unit equipment.
Device
number 11—multifunction device A
device that performs three or more
Comparatively important functions that could only be designated
by
combining several device function numbers. All of the
functions performed by device 11
shall be defined in the drawing
legend,
device function definition list or relay setting record.
NOTE — If only two relatively important
functions are p
performed by the device, it is preferred that both
function numbers be used.
Device
number 12—overspeed device A device, usually direct connected, that
operates
on machine overspeed.
Device
number 13—synchronous-speed device A device such as a centrifugal-
speed
switch, a slip-frequency relay, a voltage relay, an
undercurrent relay, or any other type of device that operates at
approximately the synchronous speed of a machine.
a machine
falls below a predetermined value.
Device
number 15—speed or frequency matching device A device that
functions
to match and hold the speed or frequency of a machine
or a
system equal to, or approximately equal to, that of another
machine,
source, or system.
Device
number 16—not used Reserved for future application.
Device
number 17—shunting or discharge switch A device that serves to open
or close a
shunting circuit around any piece of apparatus (except a
resistor),
such as a machine field, a machine armature, a capacitor,
or a
reactor.
NOTE
— This excludes devices that perform such shunting
operations as may be necessary in the process of
starting a machine by devices 6 or 42 (or their
equivalent) and also excludes device function 73 that
serves for the switching of resistors.
Device
number 18—accelerating or decelerating device
A device that is used
to close
or cause the closing of circuits that are used to increase or
decrease
the speed of a machine.
Device
number 19—starting-to-running transition contactor A device that
operates
to initiate or cause the automatic transfer of a machine
from the
starting to the running power connection.
Device
number 20—electrically operated valve An electrically operated,
controlled, or monitored device used in a fluid, air, gas, or
vacuum
line.
Device
number 21—distance relay A device that functions when the circuit
admittance, impedance,or reactance increases or decreases
beyond a
predetermined value.
Device
number 22—equalizer circuit breaker A device that serves to control or
make and
break the equalizer or the current-balancing connections
for a
machine field, or for regulating equipment, in a multiple-unit
installation.
Device number 23—temperature control
device A device that functions to
control the temperature of a machine or other apparatus, or of any
medium,
when its temperature falls below or
rises above a
predetermined value.
NOTE — An example is a thermostat that
switches on a space
heater in a switchgear assembly
when the temperature
falls to a desired value. This should be distinguished
from a device that is used to provide automatic
temperature regulation between close limits and would
be designated as device function 90T.
Device
number 24—volts per hertz relay A device that operates when the ratio of
voltage to frequency is above a preset value or is below
a
different
preset value. The relay may have any combination of
instantaneous or time delayed characteristics.
Device
number 25—synchronizing or synchronism-check relay
A synchronizing device produces an output
that causes closure at
zero-phase angle difference between two circuits. It may or may
not
include voltage and speed control. A synchronism- check relay
permits
the paralleling of two circuits that are within prescribed
limits of voltage magnitude, phase angle,
and frequency.
Device
number 26—apparatus thermal device A device that functions when the
temperature of the protected apparatus (other than the load-
carrying windings of
machines and transformers as covered by
device
function number 49) or of a liquid or other
medium
exceeds a
predetermined value; or when the temperature of the
protected
apparatus or of any medium decreases below a
predetermined value.
Device
number 27—undervoltage relay A device that operates when its input
voltage is less
than a predetermined value.
Device
number 28—flame detector A device that monitors the presence of the
pilot
or main
flame in such apparatus as a gas turbine
or a steam boiler.
Device
number 29—isolating contactor or switch A device that is used
expressly
for disconnecting one circuit from another for the
purposes
of emergency operation, maintenance, or
test.
Device
number 30—annunciator relay A nonautomatically reset device that gives
a number
of separate visual indications upon the functioning of
protective
devices and that may also be arranged to
perform a
lockout
function.
Device
number 31—separate excitation device A device that connects a circuit,
such as
the shunt field of a synchronous converter, to a source of
separate
excitation during the starting sequence.
Device
number 32—directional power relay A device that operates on a
predetermined value of power flow in a given direction such as
reverse
power flow resulting from the motoring of a generator
upon loss
of its prime mover.
Device
number 33—position switch A device that makes or breaks contact when
the main
device or piece of apparatus that has no device function
number
reaches a given position.
multi-contact switch, or the equivalent, or a programmable device,
that
establishes or determines the operating sequence of the major
devices in equipment during starting and
stopping or during
sequential
switching operations.
Device
number 35—brush-operating or slip-ring short-circuiting device
A device for raising, lowering, or shifting
the brushes of a
machine;
short-circuiting its slip rings; or engaging or disengaging
the
contacts of a mechanical rectifier.
Device
number 36—polarity or polarizing voltage device
A device that
operates,
or permits the operation of, another device on a
predetermined polarity only or that verifies the presence of a
polarizing voltage in
equipment.
Device
number 37—undercurrent or underpower relay
A device that
functions
when the
current or power flow decreases below a predetermined
value.
Device number
38—bearing protective device A device that functions on
excessive
bearing temperature or on other abnormal mechanical
conditions associated with the bearing, such as undue wear,
which may
eventually result in excessive bearing
temperature or failure.
Device
number 39—mechanical condition monitor A device that functions upon
the occurrence of an abnormal
mechanical condition (except that
associated with bearings as covered
under device function 38),
such as
excessive vibration, eccentricity, expansion,
shock,
tilting,
or seal failure.
Device
number 40—field relay A device that functions on a given or
abnormally
high or
low value or failure of machine field current, or on an
excessive
value of the reactive component of
armature current in
an ac
machine indicating abnormally high or low field excitation.
Device
number 41—field circuit breaker A device that functions to apply or
remove
the field excitation of a machine.
Device
number 42—running circuit breaker A device whose function is to
connect a
machine to its source of running or operating voltage.
This
function may also be used for a device,
such as a contactor,
that is
used in series with a circuit breaker or other fault- protecting
means,
primarily for frequent opening and closing of the circuit.
Device
number 43—manual transfer or selector device
A manually operated
device
that transfers control or potential circuits in order to modify
the plan
of operation of the associated equipment or of some of
the
associated devices.
the next
available unit in multiple-unit equipment upon the failure
or
non-availability of the normally Preceding unit.
Device
number 45—atmospheric condition monitor
A device that
functions
upon the
occurrence of an abnormal atmospheric condition, such
as
damaging fumes, explosive mixtures,
smoke, or fire.
Device
number 46—reverse-phase or phase-balance current relay A device
in a
polyphase circuit that operates when the polyphase currents
are of
reverse-phase sequence or when the polyphase currents are
unbalanced
or when the negative phase-sequence current exceeds
a preset
value.
Device
number 47—phase-sequence or phase-balance voltage relay
A device in a polyphase circuit that functions upon a redetermined
value of
polyphase voltage in the desired phase sequence, when
the
polyphase voltages are unbalanced, or when the negative
phase-sequence voltage exceeds a preset value.
Device
number 48—incomplete sequence relay A device that generally returns
the
equipment to the normal or off position
and locks it out if the
normal
starting, operating, or stopping sequence is not properly
completed
within a predetermined time.
Device number 49—machine or transformer
thermal relay A device that
functions when the temperature of a machine armature winding
or other
load-carrying winding or element of a machine or power
transformer exceeds a predetermined value.
Device
number 50—instantaneous overcurrent relay
A device that operates with no
intentional time delay when the
current
exceeds a preset value.
Device
number 51—ac time overcurrent relay A device that functions when the
ac input
current exceeds a predetermined value, and in which the
input
current and operating time are inversely related through a
substantial portion of the performance range.
Device
number 52—ac circuit breaker A device that is used to close and
interrupt
an ac power circuit under normal conditions or to
interrupt
this circuit under fault or emergency
conditions.
Device
number 53—exciter or dc generator relay
A device that forces
the dc
machine
field excitation to build up during
starting or that
functions when the machine voltage has built up to a given value.
Device
number 54—turning gear engaging device
A device either
electrically
operated,
controlled, or monitored that functions to cause the
turning
gear to engage (or disengage) the machine shaft.
Device
number 55—power factor relay A device that operates when the power
factor in
an ac circuit rises above or falls below a predetermined
value.
Device
number 56—field application relay A device that automatically controls
the
application of the field excitation to an ac motor at some
predetermined point in the slip cycle.
Device
number 57—short-circuiting or grounding device
A device that
functions
to short-circuit or ground a circuit in response to
automatic
or manual means.
Device
number 58—rectification failure relay A device that functions if a power
rectifier fails to conduct or
block properly.
Device
number 59—overvoltage relay A device that operates when its input
voltage
exceeds a predetermined value.
Device
number 60—voltage or current balance relay
A device that
operates on
a given
difference in voltage, or current input
or output, of two
circuits.
Device
number 61—density switch or sensor A device that operates at a given
density
value or at a given rate of change of
density.
Device
number 62—time-delay stopping or opening relay
A device that
imposes a
time delay in conjunction with the device that initiates
the
shutdown, stopping, or opening operation in an automatic
sequence
or protective relay system.
Device
number 63—pressure switch A device
that operates at a given pressure
value or
at a given rate of change of pressure.
Device
number 64—ground detector relay A device that operates upon failure of
machine
or other apparatus insulation to ground.
NOTE
— This function is not applied to a device connected in
the secondary circuit of current transformers in a
normally
grounded power system where other
vercurrent device numbers with the suffix G or N
should be used; for
example,51N for an ac time
overcurrent relay connected in the secondary
neutral of the current transformers.
Device
number 65—governor A device consisting of an assembly of fluid,
electrical, or mechanical control equipment used for regulating
the flow
of water, steam, or other media to the prime mover for
such
purposes as starting, holding speed or load, or stopping.
Device
number 66—notching or jogging device A device that functions to allow
only a
specified number of operations of a
given device or piece
of
equipment, or a specified number of successive operations
within a
given time of each other. It is also a device that functions
to
energize a circuit periodically or for fractions of specified
time
intervals, or that is used to permit intermittent acceleration
or jogging of a machine at low speeds for mechanical
positioning.
Device number 67—ac directional overcurrent relay A device that functions at
a desired
value of ac overcurrent flowing in a predetermined
direction.
Device
number 68—blocking or “out-of-step” relay
A device that
initiates a
pilot
signal for blocking of tripping on external faults in a
transmission line or in other
apparatus under predetermined
conditions, or cooperates with other devices to block tripping or
reclosing
on an outof- step condition or on power swings.
Device
number 69—permissive control device A device with two-positions that
in one
position permits the closing of a circuit breaker, or the
placing
of a piece of equipment into operation, and in the other
position,
prevents the circuit breaker or the equipment from being
operated.
Device
number 70—rheostat A device used to vary the resistance in an
electric
circuit
when the device is electrically operated or has other
electrical
accessories, such as auxiliary, position, or limit
switches.
Device
number 71—level switch A device that operates at a given level
value, or
on a given
rate of change of level.
Device
number 72—dc circuit breaker A device that is used to close and interrupt
a dc power
circuit under normal conditions or to interrupt this
circuit
under fault or emergency conditions.
Device
number 73—load-resistor contactor A device that is used to shunt or
insert a
step of load limiting, shifting, or indicating resistance in a
power
circuit; to switch a space heater in circuit; or to switch a
light or regenerative load resistor of a power
rectifier or other
machine
in and out of circuit.
Device
number 74—alarm relay A device other than an annunciator, as
covered
under
device function 30, that is used to operate, or that operates
in connection with, a visual or audible alarm.
Device
number 75—position changing mechanism A device that is used for
moving a main device from one position
to another in equipment;
for
example, shifting a removable circuit breaker unit to and from
the
connected, disconnected, and test positions.
Device
number 76—dc overcurrent relay A device that functions when the
current
in a dc circuit exceeds a given value.
Device
number 77—telemetering device A
transmitting device used to generate
and
transmit to a remote location an electrical signal representing
a
measured quantity; or a receiver used to receive the electrical
signal
from a remote transmitter and convert the signal
to
represent the original measured quantity.
Device number 78—phase-angle measuring relay A device that functions at a
predetermined phase angle between two voltages, between two
currents,
or between voltage and current.
Device
number 79—reclosing relay A device that controls the automatic
reclosing
and
locking out of an ac circuit
interrupter.
Device
number 80—flow switch A device that operates at a given flow value,
or at
a given
rate of change of flow.
Device
number 81—frequency relay A device that responds to the frequency of an
electrical
quantity, operating when the frequency or rate of change
of
frequency exceeds or is less than a
predetermined value.
Device
number 82—dc load-measuring reclosing relay
A device that
controls
the
automatic closing and reclosing of a dc circuit interrupter,
generally
in response to load circuit conditions.
Device
number 83—automatic selective control or transfer relay A device
that
operates to select automatically between certain sources or
conditions
in equipment or that performs a transfer operation
automatically.
Device
number 84—operating mechanism A device consisting of the complete
electrical mechanism or
servomechanism, including the
operating motor, solenoids, position
switches, etc., for a tap
changer,
induction regulator, or any similar piece of
apparatus
that
otherwise has no device function number.
Device
number 85—carrier or pilot-wire relay A device that is operated or
restrained by a signal transmitted or received via any
communications media used for relaying.
Device
number 86—lockout relay A device that trips and maintains the
associated
equipment
or devices inoperative until it is reset by an operator,
either
locally or remotely.
Device number
87—differential protective relay A device that operates on a
percentage, phase angle, or other quantitative difference of two or
more
currents or other electrical quantities.
Device
number 88—auxiliary motor or motor generator
A device used for
operating
auxiliary equipment, such as pumps, blowers, exciters,
rotating
magnetic amplifiers, etc.
Device
number 89—line switch A device used as a disconnecting,
load-interrupter,
or
isolating switch in an ac or dc power circuit. (This device
function
number is normally not necessary unless
the switch is
electrically operated or has electrical accessories, such as an
auxiliary
switch, a magnetic lock, etc.)
Device
number 90—regulating device A
device that functions to regulate a
quantity
or quantities, such as voltage, current, power, speed,
frequency, temperature, and load, at a
certain value or between
certain (generally close)
limits for machines, tie lines, or other
apparatus.
Device
number 91—voltage directional relay A device that operates when the
voltage across an open circuit breaker or contactor exceeds a
given
value in a given direction.
Device
number 92—voltage and power directional relay
A device that permits
or causes the connection of two circuits when the voltage
difference
between them exceeds a given value in a predetermined
direction
and causes these two circuits to be disconnected from
each other
when the power flowing between them exceeds a
given
value in the opposite direction.
Device
number 93—field-changing contactor A device that functions to
increase
or decrease, in one step, the value of
field excitation on a
machine.
Device
number 94—tripping or trip-free relay A device that functions to trip a
circuit
breaker, contactor, or equipment; to permit immediate
tripping
by other devices; or to prevent immediate reclosing of a
circuit
interrupter if it should open automatically, even though its
closing
circuit is maintained closed.
Device
numbers 95–99—used only for specific applications These device
numbers are used in individual
specific installations if
none of the functions assigned to the
numbers
from 1 through 94 are suitable.
Addition of prefixes and suffixes
Letters and numbers may be used as prefixes or suffixes to device
function numbers to provide a more specific definition of the function, as
discussed below. They permit a manifold multiplication of available function
designations for the large number and variety of devices used in the many types
of equipment covered by this standard.
They may also serve to denote individual or
specific parts or auxiliary contacts of these devices or certain distinguishing
features, characteristics, or conditions that describe the use of the device or
its contacts in the equipment. Prefixes and suffixes should, however, be used
only when they accomplish a useful purpose. For example, when all of
the devices in a piece of equipment are
associated with only one kind of apparatus, such as a feeder, motor, or generator, it is common practice, in order to
retain maximum simplicity in device function identification, not to add the
respective suffix letters F, M, or G to any of the device function numbers. In order to prevent any possible conflict or
confusion, each letter suffix should preferably have only one meaning in
individual pieces of equipment. However, each suffix should not consist of
more than three (and preferably not more than two) letters, in order to keep
the complete function designation as short and simple as possible. The meaning
of each suffix should be designated on the drawings or in the publications with
which they are used, similar to TC-trip coil, V-voltage, X-auxiliary relay.
In cases where the same suffix (consisting of one letter or a
combination of letters) has different meanings in the same equipment depending
upon the device function number with which it is used, then the complete device
function number with its suffix letter or letters and its corresponding
function definition should be listed in the legend in each case, i.e.,
63V-vacuum relay, 70R-raising relay for device 70, 90V-voltage regulator.
Suggested prefixes
A similar series of
numbers, prefixed by the letters RE (for remote) may be used for the
interposing relays performing functions that are controlled directly from the
supervisory system. Typical examples of such functions are RE1, RE5,
and RE94. In multiple-unit installations, it
may be desirable to use a prefix number to distinguish between device functions
associated with individual units. For example, in pipeline pump stations, the
numbers 1–99 are applied to device functions that are associated with the
overall station operation. A similar series of numbers, starting with 101
instead of 1, are used for those device functions that are associated with unit
1; a similar series starting with 201 for device functions that are associated
with unit 2; and so on, for each unit in these installations.
Suggested suffix letters
Auxiliary devices
These letters denote separate auxiliary devices, such as the following:
C Closing relay/contactor
CL Auxiliary relay, closed (energized when
main device is in closed position)
CS Control switch
D “Down” position switch relay
L Lowering relay
O Opening relay/contactor
OP Auxiliary relay, open (energized when main
device is in open position)
PB Push button
R Raising relay
U “UP” position switch relay
X Auxiliary relay
Y Auxiliary relay
Z Auxiliary relay
NOTE — In the control of a circuit breaker
with a so-called X-Y relay control scheme, the X relay is the device whose main
contacts are used to energize the closing coil or the device that in some other
manner, such as by the release of stored energy, causes the breaker to close.
The contacts of the Y relay provide the antipump feature of the circuit
breaker.
Actuating
quantities
These letters indicate the condition or
electrical quantity to which the device responds, or the medium in which it is
located, such as the following:
A Air/amperes/alternating
C Current
D Direct/discharge
E Electrolyte
F Frequency/flow/fault
GP Gas pressure
H Explosive/harmonics
I0 Zero sequence current
I-, I2 Negative sequence current
I+, I1 Positive sequence current
J Differential
L Level/liquid
P Power/pressure
PF Power factor
Q Oil
S Speed/suction/smoke
T Temperature
V Voltage/volts/vacuum
VAR Reactive power
VB Vibration
W Water/watts
Main device
The following letters denote the main device
to which the numbered device is applied or is related:
A Alarm/auxiliary power
AC Alternating current
AN Anode
B Battery/blower/bus
BK Brake
BL Block (valve)
BP Bypass
BT Bus tie
C Capacitor/condenser/compensator/carrier
current/case/compressor
CA Cathode
CH Check (valve)
D Discharge (valve)
DC Direct current
E Exciter
F Feeder/field/filament/filter/fan
14 Copyright ã 1997
IEEE All Rights Reserved
H Heater/housing
L Line/logic
M Motor/metering
MOC Mechanism operated contact4
N Network/neutral5
P Pump/phase comparison
R Reactor/rectifier/room
S
Synchronizing/secondary/strainer/sump/suction (valve)
T Transformer/thyratron
TH Transformer (high-voltage side)
TL Transformer (low-voltage side)
TM Telemeter
TOC Truck-operated contacts6
TT Transformer (tertiary-voltage side)
U Unit
Main device parts
These letters denote parts of the main
device, except auxiliary contacts, position switches, limit switches, and
torque
BK Brake
C Coil/condenser/capacitor
CC Closing coil/closing contactor
HC Holding coil
M Operating motor
MF Fly-ball motor
ML Load-limit motor
MS Speed adjusting or synchronizing motor
OC Opening contactor
S Solenoid
SI Seal-in
T Target
TC Trip coil
V Valve
Other suffix
letters
A Accelerating/automatic
B Blocking/backup
BF Breaker failure
C Close/cold
D Decelerating/detonate/down/disengaged
E Emergency/engaged
F Failure/forward
GP General purpose
H Hot/high
3Suffix
N is preferred when the device is connected in the residual of a polyphase
circuit, is connected across a broken delta, or is internally derived from the
polyphase current or voltage quantities. The suffix G is preferred where the
measured quantity is in the path to ground or, in the case of ground fault
detectors, is the current flowing to ground. See A.2 in Annex A for examples. 4MOC
denotes a circuit breaker mechanism-operated auxiliary switch that is mounted
on the stationary housing of a removable circuit breaker.
6TOC
denotes a circuit breaker truck-operated auxiliary switch that is mounted on
the stationary housing of a removable circuit breaker.
HIZ High impedance fault
HR Hand reset
HS High speed
L Left/local/low/lower/leading
M Manual
O Open/over
OFF Off
ON On
P Polarizing
R
Right/raise/reclosing/receiving/remote/reverse
S Sending/swing
SHS Semi-high speed
T Test/trip/trailing
TDC Time-delay closing contact
TDDO Time delayed relay coil drop-out
TDO Time-delay opening contact
TDPU Time delayed relay coil pickup
THD Total harmonic distortion
U Up/under
Suffix
numbers
If two or more devices with the same function
number and suffix letter (if used) are present in the same piece of equipment,
they may be distinguished by numbered suffixes, as, for example, 4X-1, 4X-2,
and 4X-3, when necessary.
Devices performing more than one function
If one device performs two important
functions in a piece of equipment so that it is desirable to identify both of
these functions, a double function number and name, such as 50/51 instantaneous
and time overcurrent relay may be used.
Device contacts
Auxiliary, position, and limit switch contacts
The letters a and b shall be
used for all auxiliary, position, and limit switch contacts for such devices
and equipment as circuit breakers, contactors, valves and rheostats, and
contacts of relays as follows:
a Contact that is open when the main device is in the standard reference
position, commonly referred to as the nonoperated or de-energized position, and
that closes when the device assumes the opposite position b Contact that
is closed when the main device is in the standard reference position, commonly
referred to as the non
Operated or de-energized position, and that
opens when the device assumes the opposite position
The simple designation a or b is
used in all cases where there is no need to adjust the contacts to change
position at any particular point in the travel of the main device or where the
part of the travel where the contacts change position is of
no significance in the control or operating
scheme. Hence, the a and b designations usually are sufficient
for circuit breaker auxiliary switches.